CE Certified Portable Residual Current Device (PRCD);EU Directives 89/336/EEC
− Electromagnetic Compatibility Directive,72/23/EEC − Low Voltage Equipment
Directive & IEC 61540 − International standard for PRCD's. Available
120V − 230V,6mA − 30mA trip levels. Applications include:
 |
 |
Pressure Washers |
 |
 |
Drain Snakes |
 |
Floor Cleaners |
 |
Industrial Appliances |
 |
Power Tools |
 |
Pumps |
 |
Boat Lifts |
 |
Extension Cords |
 |
Construction Sites |
|
|
To prevent unmonitored equipment startup,manual reset is required after
PRCD trip and power outage.
|
 |
| Model 47000 |
 |
Model 47010 |
 |
Volts/Amps:120V/16A |
 |
Volts/Amps:230V/16A |
 |
Accepts:1.5 - 2.5mm2 conductor/7.8-16.2mm dia.Cord Setsl |
 |
Accepts:1.5 - 2.5mm2 conductor/7.8-16.2mm dia.Cord Sets |
 |
Trip Level: 6 mA max. |
 |
 |
Trip Level: 10 mA max. |
 |
 |
CECompliant |
 |
CECompliant |
| Model 47020 |
 |
Model 47030 |
 |
Volts/Amps:230V/16A |
 |
Volts/Amps:230V/16A |
 |
Accepts:1.5 - 2.5mm2 conductor/7.8-16.2mm dia.Cord Sets |
 |
Accepts:1.5 - 2.5mm2 conductor/7.8-16.2mm dia.Cord Sets |
 |
Trip Level: 6 mA max. |
 |
 |
Trip Level: 30 mA max. |
 |
 |
CECompliant |
 |
CECompliant |
|
 |
| Operating Voltage Range |
 |
120/127 or 230V nominal @ 50/60 Hz |
| Operating Load Current |
16 amps max. |
| Residual Current Trip Window |
6,10,30mA |
| Response Time |
40mS max at 5(IΔn) |
| Contacts |
Normally Open (Manual Reset)
Contacts open with loss of power |
| Environmental Rating |
IP-54 |
|
 |
|
 |
 |
 |
Tested by Recognized Third Party Safety Body.
Declaration of Conformity Available. |
|